    Ati Aerosol Photometer For Cleanroom HVAC System

    Ask Lasest Price
    Brand Name : SUJING
    Model Number : APM-18
    Price : Negotiable
    Payment Terms : T/T
    Supply Ability : 800/per month
    Delivery Time : 5 work days
    • Product Details
    • Company Profile

    Ati Aerosol Photometer For Cleanroom HVAC System

    Ati Aerosol Photometer For Cleanroom HVAC System


    The ati Aerosol photometers fpr cleanroom hvac system are primarily used to check for small pinholes and other damage in filter media, such as frame seals, gasket seals, and leaks in the filter frame. By checking the tightness of the high-efficiency filter and its connection with the installation frame, find the defects of the high-efficiency filter itself and its installation in time, and take corresponding remedial measures to ensure the cleanliness of the area.


    Features and Benefits of aerosol photometer

    • long life laser light source;
    • high precision photoelectric multiplier tube detection;
    • can set PAO, DOP and other types of aerosols;
    • equipped with a dedicated handheld device to achieve control, display and sampling function;
    • large capacity data storage, real-time data storage;
    • more than the setting alarm sound and light alarm;
    • can be obtained by U disk or thermal printer to print historical data;
    • can print leakage rate and other monitoring data in real time;
    • through the special software, the sampling data can be imported into PC;
    • automatic fault detection.

    Application of digital aerosol photometer

    • leakage detection of clean room
    • VLF bench
    • biosafety cabinet
    • glove box
    • HEPA vacuum cleaner
    • HVAC system
    • HEPA filter
    • negative pressure filtering system
    • operating theatre
    • nuclear filter system
    • collection protect filter
    APM-18 photometer Specifications
    Dynamic RangeUp to 600 micrograms per liter
    Reagent SettingsPAO-4, DOP, Ondina, Mineral Oil, Paraffin
    Auto ZeroAutomatically establishes zero reading at startup
    Sensitivity1% of readings ≥0.01% to 100%
    Repeatability0.5% of readings ≥0.01% to 100%
    Flow ControlPulse Width Modulation (PWM) control ensures sampling rate of 1cfm (28.3lpm) +/- 10% in all applications.
    Light SourceSolid State, rated for life of instrument
    ReportingContinuous, Summary, and Monitoring modes
    AlarmUser selectable audible, visual, and vibratory alarms notify the user when the user defined set point is exceeded.
    Size260 (W)X160(H)X360(D)
    Weight10Kg
    OutputWireless printer, USB interface
    Power220VAC, 50/60HZ
    Standards complianceNSF 49, IEST, ISO-14644

    Ati Aerosol Photometer For Cleanroom HVAC System